TRITON XC500K - 500 KW CUMMINS K FULLY PACKAGED GENERATOR SET 552081
Model XC500KSpecifications
New
1 Year Factory Warranty
Automatic Starting System (to work with Automatic Transfer Switch)
Battery Charging Alternator
Digital Control Panel
Electric Start
Factory Loadbank Tested
Remote Breaker
Skid Mounted
Spring Mounted Vibration Isolators
Dimensions (L x W x H – height does not include muffler): 133.8” x 51.18” x 82.67”
500 KW
Weight (Pounds): 8291
Control Panel: Deep Sea Model 5210
8 Hour Base Mounted Fuel Tank
Stamford Newage Generator End
Diesel
Governor: Electronic Governor
12 Lead
3 Phase
Reconnectable
Deep Sea Control Panel 5210 Model 5210 is an Automatic Engine Control Module. The module is used to automatically start and stop the engine, indicating the operational status and fault conditions, automatically shutting down the engine and indicating an engine failure by means of an LCD display and an appropriate flashing LED on the front panel. Selected timers and alarms can be altered by the customer from the front panel. Alterations to the system are made using the 810 interface and a PC. This interface also provides real-time diagnostic facilities.
It is possible to monitor operation of the system either locally or remotely. (Optional: remote communications output versions only.)
5210 Easy Pushbutton Control Operation of the module is via pushbutton controls (with security locking facility) mounted on the front panel with STOP/RESET, AUTO, MANUAL, and START buttons. The first three buttons feature LED ‘selected’ indications. Further buttons provide LCD DISPLAY SCROLL and EVENT LOG VIEW functions.
5210 Microprocessor Control The module features 16 bit microprocessor control and a comprehensive list of timers and pre-configured sequences. This allows demanding specifications to be achieved. Configurable expansion facilities are also provided.
5210 Metering The 5210 module provides metering via the LCD display with the following instrumentation displays, accessed via the LCD DISPLAY SCROLL push buttons:
- Generator Volts L1-N, L2-N, L3-N
- Generator Volts L1-L2, L2-L3, L3-L1
- Generator Amps L1, L2, L3
- Generator Frequency Hz
- Engine Speed RPM
- Engine Oil Pressure
- Fuel Level %
- Engine Temperature
- Plant Battery Volts
- Engine Hours Run
- Generator kVA
- Generator kW
Weight 8291